CONDUCTOR
The conductors, drawn from bright electrolytic grade copper are annealed and bunched together.
INSULATION
The bunched conductors are insulated with a Specially Formulated grade of Halogen Free Flame Retardant (HFFR) compound is used. The insulation does not melt of drip in case of fire. The smoke emitted is transparent, non-toxic and minimal. The victims trapped in the fire do not suffocate and evacuation is convenient.
MARKING
The cables are printed with generic marking "AXELON SUPRIMO HFFR"
COLOURS
Red, Yellow, Blue, Black, Green, Grey & White. Other Colors available on Request.
PACKING
Packing 90 meters / 180 meters / 270 meters / 100 yards
SIZE, DIMENSIONS & RATINGS
SINGLE CORE UNSHEATHED CABLES IN VOLTAGE GRADE 1.1 KV AS PER IS: 694
Nominal Cross Sectional Area of Conductor |
Number / Nom. Dia of Wires (Nom.) |
Thickness of Insulation (Nom.) |
Overall Diameter Max. |
Current Capacity #2 Cables Single Phase AC or DC
|
D.C.Resistance (Max.) at 20°c |
|||
---|---|---|---|---|---|---|---|---|
Sq. mm | Number / mm | mm | mm | Amps | Amps | Ohm / km | ||
0.75 | 24/0.20** | 0.60 | 2.35 | 8.00 | 8.00 | 26.00 | ||
1.00 | 14/0.30* | 0.70 | 2.75 | 11.00 | 12.00 | 18.10 | ||
1.50 | 22/0.30* | 0.70 | 3.00 | 14.00 | 17.00 | 12.10 | ||
2.50 | 36/0.30* | 0.80 | 3.70 | 19.00 | 22.00 | 7.41 | ||
4.00 | 56/0.30** | 0.80 | 4.10 | 26.00 | 30.00 | 4.95 | ||
6.00 | 84/0.30** | 0.80 | 4.60 | 32.00 | 37.00 | 3.30 |
# As per IS 3961 (PART V) - 1968. The number & diameter of conductor strands are for reference only and governed by conductor resistance. The above data is indicative only and may be revised without prior information. Axelon will not be responsible for any damages arising out of incorrenct application of its proudct.
* As per conductor class 2 of IS:8130/1984 | ** As per conductor class 5 of IS:8130/1984