APPLICATION

These wires/cables are used for wiring in control panels, machines and various electrical installations in dry and damp interiors especially under typical industrial environmental conditions.

INSULATION

The conductors are insulated with specially formulated FR pvc compound with a high insulation resistance value. The insulation process is carried out on modern high speed extrusion lines, which ensures high accuracy and consistency in performance. Flame Retardant properties enable the cable to withstand overloads. The insulation is resistant to boiling water, steam and vapours. This prevents ageing and cracking in kitchens, bathrooms, damp walls and chemical industries.

MARKING

The cables are printed with generic marking ACE - FR - LF

COLOURS

Red, Yellow, Blue, Green, Black, Yellow/green, Grey, White. Other colors available on request.

PACKING

100 mtr colis packed in Plastic Wrapper and packed in protective cartons, 500 mtrs in wooden drums.

 

CABLE STRUCTURE : SINGLE CORE FLEXIBLES

Features FR FRLS HFFR
Type of Insulation 70°c / 105°c Heat Resistant PVC Flame Retardant Low Smoke (FRLS) Halogen Free(HFFR)
From 1.0 to 4.0 Sq.mm.
Type of Applications Wiring of panels for use in high ambient temperature Wiring in High density critical installations in public places and fire prone areas Wiring in high density critical installations in public places and vicinity of electronic systems
Applications Standards IS-694, BS 6004, IEC 60227, DIN VDE-0281-3 IEC 60332-1, BS 4066-1, EIC-60754-1, ASTMD-2843, ASTMD-2863 IEC 60332-1&3, BS 4066-1&3, IEC 60754-1&2, ASTMD-2563, BS 7211, DIN VDE-0282-9

SIZE, DIMENSIONS & RATINGS

Nominal Cross
Sectional Area
of Conductor
Number / Nom.
Dia of
Wires* (Nom.)
Thickness of
Insulation (Nom.)
Overall Diameter
Max.
Current Rating
Casting
D.C.Resistance
(Max.) at 20°c
Sq. mm Number / mm mm mm Amps Ohm / km
0.75 24/0.20 0.6 2.8 9.00 26.00
1.00 32/0.20 0.6 3.0 14.00 19.5
1.50 30/0.25 0.6 3.8 18.00 13.3
2.50 50/0.25 0.7 4.0 24.00 7.98
4.00 56/0.30 0.8 4.8 32.00 4.95
6.00 84/0.30 0.8 6.4 42.00 3.30
10.00 80/0.40 1.0 6.30 55 1.91
16.00 126/0.40 1.0 7.40 75 1.21
25.00 196/0.40 1.2 9.10 100 0.780
35.00 276/0.40 1.2 10.30 125 0.554
50.00 396/0.40 1.4 12.20 165 0.386
70.00 354/0.50 1.4 14.10 240 0.272
95.00 484/0.50 1.6 16.40 300 0.206
120.00 608/0.50 1.6 18.00 325 0.161
150.00 750/0.50 1.8 20.10 352 0.129
185.00 925/0.50 2.0 22.30 415 0.106
240.00 1210/0.50 2.2 25.20 500 0.0801
300.00 1520/0.50 2.4 28.50 585 0.0641

# The number & diameter of conductor strands are for reference only and governed by conductor resistance.
The above data is indicative only and may be revised without prior information. Axelon will not be responsible for any damages arising out of incorrenct application of list proudct.
'As per IS:3961 (PART V) - 1968'

Download Catalogue